Digital Spectrum MemoryFrame MF-801B Spécifications Page 23

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 90
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 22
Earth Fault Protection Curves
M-PRO 30/40
(tolerance bands shown)
A.21
A
M-PACT
Time to trip in seconds (s)
Current I (x In)
Earth fault cropping C
trip Time = Time delay x C x I f/I
Adjustment = 1, 1.5, 2, 2.5, 3, 4, 5 & 6
Note: 1 = OFF
Indicated: C = 1.5 and 6
Earth fault pick up If
Adjustment = 0.1 to 1.0 x In
in 0.01 x In steps
Time delay has 11 settings
Inst. to 1 s in steps of 0.1 s
Indicated: Inst., 0.1 s and 1 s
Pickup If set at 0.1 x In
Time delay set at inst.
Pickup If set at 0.1 x In
Time delay set at 0.1 s
Pickup If set at 1 x In
Cropping set at 6
Time delay set at 1 s
Vue de la page 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 89 90

Commentaires sur ces manuels

Pas de commentaire